POWERNET 電源MSR 2400R
描述
2400 W 模塊化電源系統(tǒng)
電源或電池充電系統(tǒng) 并聯(lián) n+1 連接,高達(dá) 90A 串聯(lián)連接,高達(dá) 360VDC
多路輸出,± 輸出熱插拔插件模塊
模塊故障和電源警報(bào) 工作溫度 –40oC … +55 °C
POWERNET 電源MSR 2400R 系列
19” SUB-RACK UNITS |
Type | Voltage versions | Modules per rack | Power | Mechanics (w x h x d) |
MSR7110R/48 | 24V, 36V, 48V | 1…3 pcs | 800W…2400W | 19” (482mm) / 2U (88mm) / 360mm |
MSR7110R/96 | 72V, 96V | 1…3 pcs | 800W…1800W | 19” (482mm) / 2U (88mm) / 360mm |
8171178A | Cover plate for empty module place | 25TE / 2U |
RECTIFIER MODULES |
Type | Input voltage *) | Nominal Output Voltage | Voltage Setting Range | Max Output Current | Current Limit Setting | Max Power | Mechanics (w x h x d) |
ADC7180R/12 | 50…260 VAC | 12 VDC | 12-15VDC | 30 A | 0-30A | 800W | 25TE / 2U / 230mm |
ADC7180R/24 | 50…260 VAC | 24 VDC | 24-30VDC | 30 A | 0-30A | 800W | 25TE / 2U / 230mm |
ADC7180R/36 | 50…260 VAC | 36 VDC | 36-54VDC | 20 A | 0-20A | 800W | 25TE / 2U / 230mm |
ADC7180R/48 | 50…260 VAC | 48 VDC | 48-60VDC | 15 A | 0-15A | 800W | 25TE / 2U / 230mm |
ADC7180R/72 | 50…260 VAC | 72 VDC | 72-108VDC | 10 A | 0-10A | 800W | 25TE / 2U / 230mm |
ADC7180R/96 | 50…260 VAC | 96 VDC | 90-144VDC | 7.5A | 0-7.5A | 800W | 25TE / 2U / 230mm |
*) Max power 600W at DC input, reduced power 55…200VAC or 78…200VDC
INPUT
Input voltage | 55…264 VAC | 55…200VAC reduced power, see module datasheet |
| 78…360 VDC / max 600W | 78…200VDC reduced power, see module datasheet |
Frequency |
| 45...65Hz |
Safety |
| According to EN60950, Class I |
Input current |
| Max 4.5A per module |
Inrush current | Soft start | max 7A 10ms peak, otherwise less than 4.5A |
Isolation | Input / ground | 1500VAC |
| Input / outputs | 3750VAC |
| Output / ground | 500VDC |
Mains switch | Front panel with light | 12, 24, 48VDC One per PSU |
|
| 72, 96VDC One per sub-rack, max 10A current |
Mains input connector | Common input for each rectifier | IEC320 C14 male connector |
OUTPUT
Voltage Nominal voltages 12…120VDC / max 800W per module
Current Nominal current per module 0…30A / max 800W per module
Short circuit protection Rectifier modules Short circuit protected, electronic current limit MCBs on front panel ADC7110R/48 sub-rack 3 x 30A MCB in negative output
ADC7110R/96 sub-rack 3 x 10A MCB in negative output
Output connector 3 terminal groups on rear panel 3-pole 10mm2 screw terminal for each rectifier
(+ , - , PE)
Hot swap Series diode in each rectifier Hot-swap allowed,
Input and output switch at OFF poSITIon Series/parallel operations All modules can be connected in series or in parallel
CONTROLS
Input On the front panel Power switch with ON/OFF light
Output On the front panel MCB ON/OFF safety switch
ALARMS
Input failure U in nom < appr. 150VAC Normally open and closed relay contacts Output failure Module failure or output switch off Relay contact and MCB auxiliary relay Alarm connector Rear panel Removable 12-pole 2.5mm2 screw terminal
Pin configurations
1 Mains alarm COMMON
2 Mains alarm NO
3 Mains alarm NC
4 Parallel output alarm COMMON
5 Parallel output alarm NO *)
6 Series output alarm PSU1 COMMON
7 Series output alarm PSU1 NC *)
8 Series output alarm PSU2 COMMON
9 Series output alarm PSU2 NC *)
10 Series output alarm PSU3 COMMON
11 Series output alarm PSU3 NC *)
12 Not in use
*) Normally = Mains / PSU OK
ENVIRONMENTAL
Temperature range | Operating | -40°C...+70 °C, de-rating at +50°C...+70 °C |
| Storage | -40°C...+85 °C |
Cooling | ADC7180R modules | Temperature controlled fan in front panel |
Shock and vibration | IEC60068-2 | See approvals below |